Disable / re-enable outputs for routing
equipment (H2/B10)
Disabled outputs are listed in menu H4/U1.
Outputs for routing equipment (fire brigade tx / fault tx) can be
disabled and re-enabled via this menu. Disabled output will stay
disabled, until re-enabled again via this menu.
Can be useful during an installation and test period, when only local
alarms are required.
Disabled output is indicated by LEDs "Disablements" (L8) and "Fault
/ Disablements Fire brigade tx" (L15).
Text in display
Disable or re-enable
Disable zone
Disable / re-enable outputs for
routing equipment
Routing equipment for FIRE:1, FAULT:1
(1=enabled, 0=disabled)
All outputs to routing equipment for:
FIRE is disabled / FAULT is enabled
Routing equipment for FIRE:0, FAULT:1
(1=enabled, 0=disabled)
Disable / re-enable outputs for
routing equipment
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? H2
97
Comments
According to chapter
"Access", see page 81.
B10
To move the cursor, press
"". Edit and/or press "A"
to accept.
Scroll or press "Return" to
B10
return to H2.
Scroll or press "Return".