Disable / Re-Enable Outputs For Routing Equipment (H2/B10)97 - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.10
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B10
"A"
E.g. "0"
"A"
"A"
"Return"
"Return"
Rev: -
Disable / re-enable outputs for routing
equipment (H2/B10)
Disabled outputs are listed in menu H4/U1.
Outputs for routing equipment (fire brigade tx / fault tx) can be
disabled and re-enabled via this menu. Disabled output will stay
disabled, until re-enabled again via this menu.
Can be useful during an installation and test period, when only local
alarms are required.
Disabled output is indicated by LEDs "Disablements" (L8) and "Fault
/ Disablements Fire brigade tx" (L15).
Text in display
Disable or re-enable
Disable zone
Disable / re-enable outputs for
routing equipment
Routing equipment for FIRE:1, FAULT:1
(1=enabled, 0=disabled)
All outputs to routing equipment for:
FIRE is disabled / FAULT is enabled
Routing equipment for FIRE:0, FAULT:1
(1=enabled, 0=disabled)
Disable / re-enable outputs for
routing equipment
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? H2
97
Comments
According to chapter
"Access", see page 81.
B10
To move the cursor, press
"". Edit and/or press "A"
to accept.
Scroll or press "Return" to
B10
return to H2.
Scroll or press "Return".