Boot Menu - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
22.1
After any restart, required disablements have to be done.
Memory fault
In case of a fault in the S/W (system program) the following text
message will be shown in the display:
Memory fault in program area: xxx
This is also indicated by LED "System fault" (L14) and the buzzer
sounds steady (continuous). The Fault tx output is "activated".
A new download of the S/W (system program) is required.
NOTE! After SSD download (see chapter "SSD programming &
download", page 72), the following messages might be shown:
Checksum fault in downloaded data.
Control unit will now restart
FAULT: Restart code 25 addr yyyy
Date: MM-DD
Time: HH:MM
FAULT: Site specific data (SSD)
Date: MM-DD
Time: HH:MM
The last one means that the SSD have not been (correctly)
downloaded. A new SSD download has to be performed.

Boot menu

The Boot menu should be used by authorised personnel only!
NOTE! Vital data can be erased via this menu.
The Boot menu is opened as follows:
Perform a "cold restart", i.e. Power down / power up EBL128:
The following text messages will be shown in the EBL128 display:
*** EBL128 ***
Checking program memory......
And after that, for a second:
Booting......
When the text "Booting......" appears, press "Access" and 0.1 sec.
later also press "1" and the Boot menu will be shown:
1:Restart, 2:Erase memory
79
EBL128 Operating Instructions V2.0.x
Serviced

Hide quick links:

Advertisement

Table of Contents
loading