Disable Zone (H2/B1) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.1
Action
"Access"
Scroll to menu H2.
"A"
"A"
Write zone number, e.g.
"01"
"A"
"A"
"A"
"Return"
"Return"
Rev: -

Disable zone (H2/B1)

When a whole zone is disabled, all alarm points within the zone are
disabled excluding the addressable manual call points.
All zones can be disabled. Disabled zones are listed in menu H4/U1.
Disabled zones can be automatically re-enabled or they have to be re-
enabled via menu H2/B5.
Text in display
Disable or re-enable
Disable zone
Disable zone: 00
Disable zone: 01
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM
(Default is current time + 3 hours)
Zone 01 is disabled
Disable zone: 00
Disable zone
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? B1
ACCEPT? H2
86
70
Comments
According to chapter
"Access", see page 81.
Press "A" to accept.
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept.
LED "Disablements" (L8)
will light up.
If more disablements shall
be done, continue like
above. If not, press
"Return" to menu B1.
Scroll or press "Return" to
menu H2.
Scroll or press "Return".