Evacuate, Alert Annunciation
Acknowledge and Disable
These functions are only valid in some conventions.
A front with the push button (P5) is required.
See also chapters "Control & Indicating Equipment", page 14 and
"LED indicators and push buttons", page 16.

Evacuate

When the green push button "Evacuate" (P5) is pressed, all outputs
programmed for sounders (type Alarm devices)
turned ON steady (continuous). This is indicated by the following
information in the EBL128 display:
Evacuate in progress
The sounders will remain ON until they are turned OFF by pressing
the push button "Evacuate" (P5) again.
NOTE! The alarm devices (sounders) will in this case be activated
steady (continuous) irrespective of the fact that the outputs can be set
to something else for fire alarm (e.g. intermittent).

Alert Annunciation Acknowledge

The green button "Alert Annunciation Acknowledge" (P5) has the
same function as the Acknowledge button on an AA unit 1735 / 1736.

Disable

When the yellow push button "Disable" (P5) is pressed, all zones in
fire condition will be disabled.
35
EBL128 Operating Instructions V2.0.x
25
will be collectively