Sensor Values (H4/U3) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
27.3
"Access"
Scroll to menu H4.
"A"
Scroll to menu U3.
"A"
"A"
Depending on
the type, the
""
following will
be shown
""
(examples):
Rev: -

Sensor values (H4/U3)

The "Momentary" value in this menu will be updated after every
detector polling, i.e. approx. every 6
The very first week average sensor value for the 430x and 440x
detectors in NORMAL mode is calculated within 2½ minutes after
SSD download & restart. During these 2½ minutes can no fire alarm
be activated and "Weekly: 00.0%/m" will be shown. The "Weekly"
value will thereafter be updated every week.
For the 440x detectors in Advanced mode the "Weekly" value is
00.0%/m by delivery. It will be updated the very first time after 13
minutes. It will thereafter be calculated every 13
then only be changed downwards if required. After 18 hours it can be
changed downwards or upwards and after additional 18 hours (36
hours in all) it can be changed downwards or upwards and it is also
saved in the detector's EEPROM, i.e. that value will be used after the
detector has been powerless.
detectors in Advanced mode is also called the "Contamination
Compensation Value (CCV).
The "Performance factor" and "Min. / Max." values are updated each
night (00:00), i.e. the values shown are from the previous day.
"Algorithm" shows the algorithm that is currently in use.
Text in display
Present system status
Disablement
Sensor values
Start Sensor : 00-00
Type 4301/4401:
Sensor: 01-01 (technical address AAA)
Momentary: XX.X%/m
Sensor: 01-01
Perf factor: X.XX%/m
Sensor: 01-01
Current Algorithm: nnnnnn
EBL128 Operating Instructions V2.0.x
th
second.
The "Weekly" value for the 440x
ACCEPT? H4
ACCEPT? U1
ACCEPT? U3
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
103
th
minute but will
Comments
According to chapter
"Access", see page 81.
Press "A" to accept.
Write the presentation
number and/or press "A"
to accept.
This is a list in which
you can scroll or use
""
to see the next
information window for
the selected sensor.
Press "Return" back to
"Start Sensor...".
Scroll or write a new

Hide quick links:

Advertisement

Table of Contents
loading