Table 9-24 shows the interrupt event, priority, and assigned event number.
Table 9-24 Interrupt Events in Priority Order
Event Number
8
Port 0: Receive character
9
Port 0: Transmit complete
23
Port 0: Receive message complete
24
Port 1: Receive message complete
25
Port 1: Receive character
26
Port 1: Transmit complete
19
PTO 0 complete interrupt
20
PTO 1 complete interrupt
0
Rising edge, I0.0
2
Rising edge, I0.1
4
Rising edge, I0.2
6
Rising edge, I0.3
1
Falling edge, I0.0
3
Falling edge, I0.1
5
Falling edge, I0.2
7
Falling edge, I0.3
12
HSC0 CV=PV (current value = preset value)
27
HSC0 direction changed
28
HSC0 external reset
13
HSC1 CV=PV (current value = preset value)
14
HSC1 direction input changed
15
HSC1 external reset
16
HSC2 CV=PV
17
HSC2 direction changed
18
HSC2 external reset
32
HSC3 CV=PV (current value = preset value)
29
HSC4 CV=PV (current value = preset value)
30
HSC4 direction changed
31
HSC4 external reset
33
HSC5 CV=PV (current value = preset value)
10
Timed interrupt 0
11
Timed interrupt 1
21
Timer T32 CT=PT interrupt
22
Timer T96 CT=PT interrupt
S7-200 Programmable Controller System Manual
A5E00066097-02
Interrupt Description
SIMATIC Instructions
Priority
Priority Group
in Group
0
0
0
Communications
Communications
(highest)
1
1
1
0
1
2
3
4
5
6
7
8
9
10
11
Discrete (middle)
Discrete (middle)
12
13
14
15
16
17
18
19
20
21
22
23
0
1
Timed (lowest)
Timed (lowest)
2
3