S7-200 Specifications
Table A-9
Specifications for EM 223 24 VDC 8 In/8 Out, and EM 223 24 VDC 8 In/8 Relay Out
Description
Order Number
Output Current
Logic 1 signal
Number of outputs groups
Number of outputs on (maximum)
Per group - horizontal mounting (maximum)
Per group - vertical mounting (maximum)
Maximum current per common/group
Lamp load
ON state resistance (contact resistance)
Leakage current per point
Surge current
Overload protection
Isolation
Optical isolation (galvanic)
Isolation resistance
Isolation coil to contact
Isolation between open contacts
In groups of
Inductive Load Clamping
Repetitive
Energy dissipation
2
< 0.5 LI
x switching rate
Clamp voltage limits
Output Delay
Off to On
On to Off
Relay
Switching delay
Lifetime mechanical (no load)
Lifetime contacts at rated load
Cable Length
Unshielded
Shielded
Power Consumption
From +5 VDC (from I/O bus)
From L+
L+ coil power voltage range
A-34
EM 223 DI8/DO8 X DC24V
6ES7 223-1BH20-0XA0
0.75 A
2
8
4
4
3 A
5 W
0.3 Ω
µ
10
A, maximum
8 A for 100 ms, maximum
No
500 VAC for 1 minute
-
-
-
4 points
1 W, all channels
L+ minus 48V
µ
50
s, maximum
µ
200
s, maximum
-
-
-
150 m
500 m
80 mA
-
-
S7-200 Programmable Controller System Manual
EM 223 DI8/DO8 X DC24V/Rly
6ES7 223-1PH20-0XA0
2.00 A
2
8
4
4
8 A
30 W DC/200 W AC
0.2 Ω, maximum when new
-
7 A with contacts closed
No
-
100 M Ω, minimum when new
1500 VAC for 1 minute
750 VAC for 1 minute
4 points
-
-
-
-
10 ms, maximum
100,000,000 open/close cycles
100,000 open/close cycles
150 m
500 m
80 mA
9 mA per output when On
20.4 to 28.8 VDC
A5E00066097-02