S7-200 Specifications
A.12
Specifications for the EM 277 PROFIBUS-DP Module
Table A-16
Specifications for the EM 277 PROFIBUS-DP Module
Description
Order Number
Physical Size
Dimensions (W x H x D)
Weight
Power loss (dissipation)
Communication Features
Number of Ports
Electrical interface
Isolation (external signal to PLC logic)
PROFIBUS-DP/MPI baud rates (set automatically)
Protocols
Cable Length
Up to 93.75K baud
187.5K baud
500K baud
1 to 1.5M baud
3 to 12M baud
Network Capabilities
Station address settings
Maximum stations per segment
Maximum stations per network
MPI Connections
Power Consumption
+5 VDC (from I/O bus)
24 VDC Input Power Requirements
Voltage range
Maximum current
Module only with port active
Add 90 mA of 5V port load
Add 120 mA of 24V port load
Ripple noise (<10 MHz)
1
Isolated (input power to module logic)
5 VDC Power on Communication Port
Maximum current per port
Transformer isolation from module
logic and from 24 VDC input power
24 VDC Power on Communication Port
Voltage range
Maximum current per port
Current limit
Isolated
1
No power is supplied to module logic by the 24 VDC supply. 24 VDC supplies power for the communication port.
A-50
EM 277 PROFIBUS-DP
6ES7 277-0AA20-0XA0
71 mm x 80 mm x 62 mm
175 g
2.5 W
1 port
RS-485
500 VAC (Galvanic)
9.6, 19.2, 45.45, 93.75, 187.5, and 500K baud; 1, 1.5, 3, 6, and12M baud
PROFIBUS-DP slave and MPI slave
1200 m
1000 m
400 m
200 m
100 m
0 - 99 (set by rotary switches)
32
126, up to 99 EM277 stations
6 total, 2 reserved (1 for PG and 1 for OP)
150 mA
20.4 to 28.8 VDC (Class 2 or sensor power from PLC)
30 mA
60 mA
180 mA
<1 V peak to peak (maximum)
500 VAC for 1 minute
90 mA
500 VAC for 1 minute
20.4 to 28.8 VDC
120 mA
0.7 to 2.4 A
Not isolated, same circuit as input 24 VDC