S7-200 Specifications
Table A-29 Temperature Ranges ( F) for Thermocouple Types
Data Word
(1 digit = 0.1 F)
Type J
Type J
Dec
Hex
32767
7FFF
>2192.0 F
32511
7EFF
32140
7D90
27649
6C01
27648
6C00
:
:
25020
61B8
:
:
23720
5CA8
:
:
21920
55A0
2192.0 F
:
:
18320
4790
:
:
7520
1D60
:
:
320
0140
:
:
1
0001
0.1 F
0
0000
0.0 F
-1
FFFF
-0.1 F
:
:
-580
FDBC
:
:
-2380
F6B4
-238.0 F
:
:
-3280
F330
underrange
:
:
-3460
F27C
-346.0 F
:
:
-4270
EF52
:
:
-4540
EE44
:
:
-27648
9400
-27649
93FF
:
:
-32512
8100
-3268
8000
<-346.0 F
*OF = Overflow; OR = Overrange; NR = Normal range; UR = Underrange; UF = Underflow
indicates that all analog values greater than this and below the open wire threshold report the overflow data value, 32767 (0x7FFF).
indicates that all analog values less than this and greater than the open wire threshold report the underflow data value, -32768 (0x8000).
A-76
Type K
Type K
Type T
Type T
Type E
Type E
>2502.0 F
>752.0 F
>1832.0 F
2502.0 F
overrange
2372.0 F
1832.0 F
752.0 F
0.1 F
0.1 F
0.0 F
0.0 F
-0.1 F
-0.1 F
-328.0 F
underrange
-427.0 F
-427.0 F
underrange
underrange
-454.0 F
-454.0 F
-454.0 F
<-454.0 F
<-454.0 F
<-454.0 F
Type R, S
Type R, S
Type N
Type N
>3214.0 F
>2372.0 F
3214.0 F
2764.8 F
2372.0 F
752.0 F
underrange
32.0 F
0.1 F
0.1 F
0.1 F
0.0 F
0.0 F
0.0 F
-0.1 F
-0.1 F
-0.1 F
-58.0 F
underrange
-454.0 F
<-58.0 F
<-454.0 F
S7-200 Programmable Controller System Manual
80 mV
80 mV
>94.071mV
OF
94.071mV
94.071mV
OR
80.0029mV
80mV
NR
NR
0.0029mV
0.0mV
-0.0029mV
-80mV
-80.0029mV
-94.071mV
OR
<-94.07 mV
UF