Table 9-17 PTO /PWM Control Registers
Q0.0
Q0.1
SM66.4
SM76.4
PTO profile aborted due to delta calculation error
SM66.5
SM76.5
PTO profile aborted due to user command
SM66.6
SM76.6
PTO pipeline overflow/underflow
SM66.7
SM76.7
PTO idle
Q0.0
Q0.1
SM67.0
SM77.0
PTO/PWM update cycle time value 0 = no update;
SM67.1
SM77.1
PWM update pulse width time value 0 = no update;
SM67.2
SM77.2
PTO update pulse count value
SM67.3
SM77.3
PTO/PWM time base select
SM67.4
SM77.4
PWM update method:
0 = asynchronous update, 1 = synchronous update
SM67.5
SM77.5
PTO operation: 0 = single segment operation 1 = multiple segment operation
SM67.6
SM77.6
PTO/PWM mode select
SM67.7
SM77.7
PTO/PWM enable
Q0.0
Q0.1
SMW68
SMW78
PTO/PWM cycle time value (range: 2 to 65535)
SMW70
SMW80
PWM pulse width value (range: 0 to 65535)
SMD72
SMD82
PTO pulse count value (range: 1 to 4294967295)
SMB166
SMB176
Number of segment in progress (used only in multiple segment PTO operation)
SMW168 SMW178 Starting location of profile table, expressed as a byte offset from V0 (used only in
multiple segment PTO operation)
S7-200 Programmable Controller System Manual
A5E00066097-02
Status Bits
0 = no error;
1 = aborted
0 = no abort;
1 = aborted
0 = no overflow; 1 = overflow/underflow
0 = in progress;
1 = PTO idle
Control Bits
0 = no update;
0 = 1 µs/tick;
0 = selects PTO;
1 = selects PWM
0 = disables PTO/PWM;
1 = enables PTO/PWM
Other PTO/PWM Registers
SIMATIC Instructions
1 = update cycle time
1 = update pulse width
1 = update pulse count
1 = 1ms/tick
9-57