Table 9-8

HSC3 Modes of Operation (CPU 221, CPU 222, CPU 224, and CPU 226)

Mode
0
Single phase up/down counter with internal direction control
SM137.3 = 0, count down
SM137.3 = 1, count up
Table 9-9

HSC4 Modes of Operation (CPU 221, CPU 222, CPU 224, and CPU 226)

Mode
0
Single phase up/down counter with internal direction control
SM147 3 = 0 count down
SM147.3 = 0, count down
1
SM147.3 = 1, count up
3
Single phase up/down counter with external direction control
I0 4 = 0 count down
I0.4 = 0, count down
4
I0.4 = 1, count up
6
Two-phase counter with count up and count down clock
i
inputs
t
7
9
A/B phase quadrature counter,
phase A leads B by 90 degrees for clockwise rotation,
hase A leads B by 90 degrees for clockwise rotation,
phase B leads A by 90 degrees for counterclockwise
10
rotation
Table 9-10 HSC5 Modes of Operation (CPU 221, CPU 222, CPU 224, and CPU 226)
Mode
0
Single phase up/down counter with internal direction control
SM157.3 = 0, count down
SM157.3 = 1, count up
S7-200 Programmable Controller System Manual
A5E00066097-02
HSC3
Description
HSC4
Description
HSC5
Description
SIMATIC Instructions
I0.1
Clock
I0.3
I0.4
I0.5
Clock
Clock
Reset
Dir.
Clock
Clock
Reset
Clock
Clock
(Up)
(U )
(D )
(Dn)
Reset
Clock
Clock
Phase
Phase
A
A
B
B
Reset
I0.4
Clock
9-35