T-Shaped Branch Communication Specification List - Mitsubishi FX2N-16CCL-M User Manual

Cc-link master module
Hide thumbs Also See for FX2N-16CCL-M:
Table of Contents

Advertisement

FX2N-16CCL-M CC-Link System Master Block
8.5.2

T-shaped branch communication specification list

The table below shows the communication specification in T-shaped branch connection.
For communication specification not shown in the table below, refer to Section 4.4.
Table 8.2:
Item
Transmission speed
Maximum main line
length
Maximum branch line
length
Total branch line
length
Maximum number of
modules connected to
branch line
Connection cable
Terminal resistor
(connection method)
T-shaped branch
terminal block/
connector
Maximum main line
length, T-shaped
branch interval and
cable length between
modules
Terminal
resistor
Specification
625kbps
100m
50m
6 modules/branch line
Dedicated CC-Link cable
(Examples: FANC-SB, CSFV-SLAB,
100ZCLK-SB-20AWGX3C)
Connect a terminal resistor (110 Ω) packed
together with master module.
• Terminal block: Commercial one
• Connector:
Connector for FA sensor NECA4202
(IEC947-5-2) or its equivalent is
recommended.
(NECA: THE JAPAN ELECTRIC
CONTROL EQUIPMENT INDUSTRY
ASSOCIATION Standards)
Dedicated CC-Link cable (with terminal resistor of 110 Ω)
Transmission
speed
625kbps
156kbps
Maximum main line length (excluding branch line length)
*2
R
Master
station
*2
R
*1
R
(Branch line length: 8 m or less)
156kbps
500m
8m
200m
Maximum
T-shaped
main line
branch
length
interval
100m
No limit
500m
T-shaped branch interval
*2
*1
*1
R
R
R
*2
R
R
: Indicates a remote I/O station or remote device station.
Data Link Procedure 8
Remarks
10, 5 and 2.5 Mbps are not available.
The value indicates the cable length
between terminal resistors.
The cable length of T-shaped branch lines
(branch length) is not included.
The value indicates the cable length per
branch line.
The value indicates the total length of all
branch lines.
The number of connected modules
conforms to the CC-Link specification.
• Dedicated high-performance CC-Link
cables (example: FANC-SBH) are not
available.
• Cables produced by different
manufacturers are not available at the
same time.
(For manufacturers, refer to brochures.)
For the connection method, refer to Section
8.4.
• When wiring cables to the main line, strip
as little of the insulation as possible.
Cable length between
Cable length between
master station and
remote stations*1
adjacent station*2
30 cm or more
*1
*1
*1
R
R
R
*1
*1
*1
*1
R
R
R
R
(Branch line length: 8 m or less)
1 m or more
Terminal
resistor
*1
R
8-11