FX2N-16CCL-M CC-Link System Master Block
3) Master station (RWw) → remote device station (RWw)
[Calculation expression]
SM + LS × 3 + Remote device station processing time [ms]
SM : Scan time of master station's sequence program
LS : Link scan time (Refer to Section 6.2.)
[Data flow]
PLC
Buffer memory in master station
(Remote register RWw)
Link scan (LS)
Remote device station
4) Master station (RWr) ← remote device station (RWr)
[Calculation expression]
SM + LS × 2 + Remote device station processing time [ms]
SM : Scan time of master station's sequence program
LS : Link scan time (Refer to Section 6.2.)
[Data flow]
PLC
Buffer memory in master station
(Remote register RWr)
Link scan (LS)
Remote device station
TO
TO
Remote register (RWr)
Data Link Processing Time 6
Remote register (RWw)
FROM
FROM
6-6