FX2N-16CCL-M CC-Link System Master Block
2) Operation based on parameters registered in the EEPROM
a) Parameter registration procedure to the EEPROM
1.Write the parameter setting program shown below.
2.Turn ON the EEPROM registration command.
3.When parameter registration to the EEPROM is completed, the system can be
operated using only the program for "a) Operation based on parameters registered in
the EEPROM".
The parameter setting program is not required
Parameter setting program
M8000
RUN monitor
M20
Module
error
M0
M1
M1
M35
Module
ready
FROM
K0
HA
K4M20
PLS
SET
MOV
K5
MOV
K3
MOV
K2
TO
K0
H0001
D0
MOV
K0
TO
K0
H0006
D3
MOV
H0004
TO
K0
H0010
D4
MOV
H0100
TO
K0
H0014
D5
Parameter Setting 7
→M35 to M20
K1
BFM#A
H
M0
M1
Number of connected
D0
modules (5 modules)
Number of retries (3 times)
D1
D2
Number of automatic return
modules (2 modules)
K3
Operation specification
D3
against CPU down (stop)
K1
D4
Reserved station
specification
K1
D5
Invalid station
specification
K1
7-12