FX2N-16CCL-M CC-Link System Master Block
Error
code
Description
(hex.)
Number of retries
B391
setting error
(parameter)
Operation against
CPU down
B392
specification error
(parameter)
Number of
automatic return
B394
modules setting
error (parameter)
Station number
B396
overlap error
(parameter)
Station information
B397
setting error
(parameter)
Number of
occupied stations
B398
setting error
(parameter)
Number of
connected
B399
modules setting
error (parameter)
Reserved station
B39B
specification error
(parameter)
Cause of error (details)
The number of retries (address 2
(parameter) is not set inside the
range from 1 to 7.
The operation specification against
CPU down (address 6
) (parameter)
H
is not set to 0 or 1.
The number of automatic return
modules (address 3
) (parameter) is
H
not set inside the range from 1 to 10.
In the station information (addresses
20
to 2E
) (parameter), one station
H
H
number is specified twice or more.
The station information (addresses
20
to 2E
) (parameter) does not
H
H
satisfy the system configuration
condition.
In the station information (addresses
20
to 2E
) (parameter), the number
H
H
of occupied stations is not set inside
the range from 1 to 4.
The number of connected modules
(address 1
) (parameter) is not set
H
inside the range from 1 to 64.
In the reserved station specification
(parameter), all stations are set as
reserved ones.
Troubleshooting 13
Corrective action
)
H
Set a value inside the range from 1 to
7.
Set 0 or 1.
Set a value inside the range from 1 to
10.
Use each station number only once.
Set the parameters to satisfy the
condition.
Set a value inside the range from 1 to
4.
Set a value inside the specification
range (1 to 15) of the FX Series
master station.
Confirm the reserved station
specification (parameter).
13-9