Mitsubishi FX2N-16CCL-M User Manual page 136

Cc-link master module
Hide thumbs Also See for FX2N-16CCL-M:
Table of Contents

Advertisement

FX2N-16CCL-M CC-Link System Master Block
Buffer memory
Number
Number
SB0050
5E5
SB0060
5E6
SB0061
5E6
SB0065
5E6
SB006A
5E6
SB006D
5E6
SB006E
5E6
SB0073
5E7
SB0074
5E7
Name
Bit
Offline test
0
H
execution status
0
Module mode
H
1
Station type
H
Input status of data
5
H
link faulty station
Switch setting
10
H
status
Parameter setting
13
H
status
Operation status in
14
H
host station
Status of operation
3
specification
H
against CPU down
Reserved station
4
H
specification status
Description
Indicates the offline test execution status.
OFF : Not executed
ON : Being executed
Indicates the setting status of the mode setting switch
in the module.
OFF : Online (0)
ON : Other than online (0)
Indicates the setting status of the station number
setting switch in the module.
OFF : Master station (No. 0)
ON : Setting error (The station number is not set to
0.)
Indicates the setting status of the condition setting
switch (DIP switch SW4) in the module.
OFF : Clear
ON : Keep
Indicates the switch setting status.
OFF : Normal
ON : Setting error (The error code is stored in
SW006A.)
Indicates the parameter setting status.
OFF : Normal
ON : Setting error (The error code is stored in
SW0068.)
Indicates the data link operation status in the host
station.
OFF : In progress
ON : Not executed
Indicates the status of operation specification against
CPU down by parameter.
OFF : Stop
ON : Continue
Indicates the reserved station specification status by
parameter (SW0074).
OFF : Not specified
ON : Specified
Programming 9
9-8

Advertisement

Table of Contents
loading

Table of Contents