Mitsubishi FX2N-16CCL-M User Manual page 37

Cc-link master module
Hide thumbs Also See for FX2N-16CCL-M:
Table of Contents

Advertisement

FX2N-16CCL-M CC-Link System Master Block
Table 4.1:
Item
Connection cable
RAS function
Number of times of
parameter registration
to EEPROM
Connectable PLC
Number of occupied
I/O points
Communication with
PLC
Note
Operation indication
24V DC external
power supply
5V DC internal power
supply
Accessories
MASS (weight)
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be
used at the same time. Only either type of cables are available.
Attach a terminal resistor in accordance with the cable type. (Refer to Section 8.4.)
*2 When an FX
Dedicated CC-Link cable/Dedicated high-performance CC-Link cable
Automatic return function
Slave station cutoff function
Error detection by link special relay/register
Approximately 10,000 times
FX
, FX
(V 2.20 or later), FX
1N
2N
8 I/O points of FX Series PLC (8 points in total. The ratio between inputs and
outputs is arbitrary.)
By FROM/TO instructions via the buffer memory
Scan method: Asynchronous mode
Automatic refresh: Not provided
Local station function: Not provided
Standby master station function: Not provided
Intelligent device station connection function: Not provided
This master block FX
M cannot be connected at the same time.
POWER: Lit while 24V DC is supplied from outside.
L RUN : Lit while communication is normal.
L ERR : Lit when communication error has occurred.
SD
: Lit while data is being transmitted.
RD
: Lit while data is being received.
Supplied from 24V DC (150 mA) external terminal block.
5V DC is self-supplied. 5V DC of PLC is not used.
Terminal resistor
For standard cable:
110 Ω, 1/2 W (color cable: brown, brown and brown), 2 cables
For high performance cable:
130 Ω, 1/2 W (color cable: brown, orange and brown), 2 cables
Special block number label
0.4kg (0.88lbs)
Series PLC is connected, the interface FX
2NC
Specification
and FX
(V 2.20 or later)
3U
2NC
-16CCL-M and the AS-i maser block FX
2N
2NC
Specification 4
*1
*2
Series PLC
-32ASI-
2N
-CNV-IF is required.
4-3