WIRING PRECAUTIONS
• Perform Class D grounding (100Ω or less) with a wire of 2 mm
terminal in the PLC main unit. However, never perform common grounding with a high
voltage system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
Another
PLC
PLC
equipment
Dedicated grounding
Common grounding
(best)
Another
PLC
equipment
Common grounding
(allowed)
(not allowed)