LonWorks Gateway setting
LonWorks Gateway setting
System Architecture
OnOff
controller
Outdoor
Unit
Connecting outdoor units and LonWorks Gateway
- You can control up to 80 outdoor units and 128 indoor units using LonWorks Gateway.
Each communication channel of LonWorks Gateway can be connected with 16 outdoor units.
The maximum number of indoor units (including ERV and MCU) that can be connected to
each RS485 communication channel of LonWorks Gateway is 128.
- The more outdoor units are connected, the longer time takes for tracking.
For devices that support new communication, you must set the communication mode of the
channel to 'NEW' from 'System settings
conventional communication type, cannot be connected to LonWorks Gateway with new
communication.
When setting communication channel mode as 'NEW', the address of virtual OnOff control
will be assigned.
Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 3: Virtual OnOff controller 14,
Channel 4: Virtual OnOff controller 15