LonWorks Gateway setting (Continued)
Message Definition
Data for Indoor Device
● nvoSpaceTemp(11)
Description
SNVT Type
Value and operation
● nvoApplicMode(12), nviApplicMode(2)
Description
SNVT Type
Value and operation
● nvoSetpoint(13), nviSetpoint(3)
Description
SNVT Type
Value and operation
● nvoOnOff(14), nviOnOff(1)
Description
SNVT Type
Value and operation
86
E-
Indoor temperature
SNVT_temp_p: Signed Long, 2 bytes
Range: -10.00 °C ~ 50.00 °C
Operation Mode status
SNVT_hvac_mode: Enumeration(hvac_t)
0: HVAC_AUTO
1: HVAC_HEAT
3: HVAC_COOL
6: HVAC_OFF
9: HVAC_FAN_ONLY
14: HVAC_DEHUMID
❈ Invalid Value: Automatically set as HVAC_AUTO
Set Temperature
SNVT_temp_p: Signed Long, 2 bytes
Cool: 18.0 °C ~ 30.0 °C, Heat: 16.0 °C 30.0 °C
❈ Invalid Value: Automatically set up as minimum or
maximum value.
❈ When setting temperature, only an integer value is
applied. A decimal point is ignored.
Power ON/OFF status
SNVT_switch: Unsigned/signed Short
Value
OFF
0.0
ON
100.0
State
0
1