Samsung MIM–B18BN User & Installation Manual page 63

Hide thumbs Also See for MIM–B18BN:
Table of Contents

Advertisement

AHU Kit
Single AHU unit has following point list.
Instance
Object
Number
1
Indoor Temperature
2
Set temperature
Setting lower temperature
3
limit
Setting upper temperature
4
limit
The power value of an indoor
5
unit after the basic date
The number of hours usage of
6
an indoor unit after the basic
date
7
Power value within period
The number of hours usage of
8
an indoor unit within period
9
Power On/Off
Applying lower temperature
10
limit setting
Applying upper temperature
11
limit setting
12
Filter sign status
13
Filter sign reset
14
Operation mode status
15
Operation mode limit status
16
Remote controller limit status
Integrated error code of both
17
indoor unit and outdoor unit
Discharge cooling set
* 18
temperature
Discharge heating set
* 19
temperature
* 20
Discharge current temperature
* 21
Humidification setting
* 22
Outdoor air intake setting
* 23
Outdoor cooling setting
* 24
Fan speed status
* 25
Set humidity status
* 26
Current humidity status
27
AHU Notify
(*) Mark is optionally supported.
Object
Object Name
Type
AI
AHU_RoomTemp_xx_xxxxxx
AV AHU_Temp_Set_xx_xxxxxx
AV AHU_Cool_LimitTemp_xx_xxxxxx
AV AHU_Heat_LimitTemp_xx_xxxxxx
AI
AHU_Baseline_kWh_xx_xxxxxx
AI
AHU_Baseline_Minute_xx_xxxxxx Minute
AI
AHU_Period_kWh_xx_xxxxxx
AI
AHU_Period_Minute_xx_xxxxxx
BV AHU_Power_xx_xxxxxx
BV AHU_Cool_Limit_set_xx_xxxxxx
BV AHU_Heat_Limit_set_xx_xxxxxx
BI
AHU_FilterSign_xx_xxxxxx
BO AHU_FilterSign_Reset_xx_xxxxxx
MV AHU_Operation_Mode_xx_xxxxxx Auto Cool
MV AHU_Mode_Limit_xx_xxxxxx
MV AHU_Remocon_Limit_xx_xxxxxx
AI
AHU_Error_Code_xx_xxxxxx
AV AHU_DisCoolSetTemp_xx_xxxxxx
AV AHU_DisHeatSetTemp_xx_xxxxxx
AI
AHU_Dis_CurrentTemp_xx_xxxxxx
BV AHU_Humidification_xx_xxxxxx
BV AHU_OAIntake_xx_xxxxxx
BV AHU_OutdoorCool_xx_xxxxxx
MV
AHU_FanSpeed_xx_xxxxxx
MV AHU_SetHumidity_xx_xxxxxx
MI AHU_CurrentHumidity_xx_xxxxxx
NC AHU_Notify_xx_xxxxxx
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3 Text-4 Text-5
°C
°C
°C
°C
kWh
kWh
Minute
Off
On
False
True
False
True
False
True
False
True
Heat
Fan Dry
No
Cool
Heat
Limit
Only
Only
Enable
Disable
Conditional
RC
RC
RC
Refer to list of error code
°C
°C
°C
Off
On
Off
On
Off
On
Low
Mid
High
Low
Mid
High
Low
Mid
High
When the error occurred, send
event to list of destination in the
recipient_list. (Max : 8)
63
E-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents