ERV, ERV Plus
Single ERV or ERV Plus unit has following point list.
Instance
Object
Number
1
Power On/Off operation
2
Filter sign status
3
Filter sign reset
4
Operation mode status
5
Fan speed status
6
Remote controller limit status
7
Integrated error code of ERV unit
The power value of an ERV Plus unit
*8
after the basic date
The number of hours usage of an
*9
ERV Plus unit after the basic date
*10
Power value within period
The number of hours usage of an
*11
ERV Plus unit within period
*12
ERV Plus operation mode status
*13
ERV Plus operation mode limit status
14
ERV Notify
(*) Mark is optionally supported.
DVM CHILLER
Single DVM CHILLER Unit has following point list.
Instance
Object
Number
1
Chilled Water Temperature
2
Set temperature
3
Demand limit setting
The number of hours usage of an
4
indoor unit after the basic date
The number of hours usage of an
5
indoor unit within peirod
6
Power On/Off operation
7
Water Law
8
Quiet
9
Forced Fan
10
Operation mode status
11
Remote controller limit status
12
Integrated error code
13
DVM CHILLER Notify
BACnet Device Object does not support master function of
DVM CHILLER.
Demand control setting range is as follows:
50,55,60,65,70,75,80,85,90,95,100(%)
Object
Object Name
Type
BV
ERV_Power_xx_xxxxxx
BI
ERV_FilterSign_xx_xxxxxx
BO
ERV_FilterSign_Reset_xx_xxxxxx
MV
ERV_Operation_Mode_xx_xxxxxx
MV
ERV_FanSpeed_xx_xxxxxx
MV
ERV_Remocon_Limit_xx_xxxxxx
AI
ERV_Error_Code_xx_xxxxxx
AI
ERV_Plus_Baseline_kWh_xx_xxxxxx
AI
ERV_Plus_Baseline_Minute_xx_xxxxxx Minute
AI
ERV_Plus_Period_kWh_xx_xxxxxx
AI
ERV_Plus_Period_Minute_xx_xxxxxx
MV
ERV_Plus_Operation_Mode_xx_xxxxxx
MV
ERV_Plus_Mode_Limit_xx_xxxxxx
NC
ERV_Notify_xx_xxxxxx
Object
Object Name
Type
AI
MC_WaterTemp_xx_xxxxxx
AV MC_WaterTemp_Set_xx_xxxxxx
AV MC_Demand_Set_xx_xxxxxx
AI
MC_Baseline_Minute_xx_xxxxxx
AI
MC_Period_Minute_xx_xxxxxx
BV
MC_Power_xx_xxxxxx
BO MC_Water_Law_xx_xxxxxx
BV
MC_Quiet_xx_xxxxxx
BV
MC_Forced_Fan_xx_xxxxxx
MV MC_Operation_Mode_xx_xxxxxx
MV MC_Remocon_Limit_xx_xxxxxx
AI
MC_Error_Code_xx_xxxxxx
NC MC_Notify_xx_xxxxxx
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3
Text-4 Text-5
Off
On
False
True
False
True
Auto
HeatEx
Bypass
Sleep
Low
High
Turbo
Enable
Disable
Conditional
RC
RC
RC
kWh
kWh
Minute
Auto
Cool
Heat
Off
Cool
No Limit
Heat Only
Only
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3
Text-4 Text-5
°C/F
°C/F
%
Minute
Minute
Off
On
False
True
Off
On
Off
On
Cool
Hot
Cool
Heat
Storage
Water
Enable
Disable
Conditional
RC
RC
RC
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)