BACnet Gateway setting

System Architecture
OnOff
controller
RS 485
Outdoor
Unit
Connecting outdoor units and BACnet Gateway
- You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway.
Each communication channel of BACnet Gateway can be connected with 16 outdoor units.
The maximum number of indoor units (including ERV and MCU) that can be connected to
each communication channel of BACnet Gateway RS485 is 128.
- The more outdoor units are connected, the longer time takes for tracking. (Max. 30 minutes)
For devices that support new communication, you must set the communication mode of
the channel to 'NEW' from 'System settings
with conventional communication type, cannot be connected to BACnet Gateway with new
communication.
When setting communication channel mode as 'NEW', the address of virtual centralized
control will be assigned.
Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 3: Virtual OnOff controller 14,
Channel 4: Virtual OnOff controller 15