BACnet Gateway setting (Continued)
BACnet Point List

Indoor Unit

Single indoor unit has following point list.
Instance
Object
Number
1
Indoor Temperature
2
Set temperature
3
Setting lower temperature limit
4
Setting upper temperature limit
The power value of an indoor unit after
5
the basic date
The number of hours usage of an
6
indoor unit after the basic date
7
Power value within period
The number of hours usage of an
8
indoor unit within period
** 9
Power On/Off
Applying lower temperature limit
10
setting
Applying upper temperature limit
11
setting
** 12
Filter sign status
** 13
Filter sign reset
** 14
Operation mode status
* 15
Fan speed status
16
Air flow direction status
** 17
Operation mode limit status
** 18
Remote controller limit status
Integrated error code of both indoor
** 19
unit and outdoor unit
* 20
SPI setting
* 21
HumanSensor setting
** 22
AC Indoor Notify
* 23
Discharge cooling set temperature
* 24
Discharge heating set temperatrue
* 25
Discharge current temperature
Temperature setting range can be different depending on the model and the common
range is as follows:
Auto: 18 ˚C~30 ˚C
Cool: 18 ˚C~30 ˚C
Heat: 16 ˚C~30 ˚C
Fan: Temperature cannot be adjusted
Dry: 18 ˚C~30 ˚C
(*) Mark is optionally supported. For a fresh duct, (**) mark is supported.
62
E-
Object
Object Name
Type
AI
AC_RoomTemp_xx_xxxxxx
AV
AC_Temp_Set_xx_xxxxxx
AV
AC_Cool_LimitTemp_xx_xxxxxx
AV
AC_Heat_LimitTemp_xx_xxxxxx
AI
AC_Baseline_kWh_xx_xxxxxx
AI
AC_Baseline_Minute_xx_xxxxxx
AI
AC_Period_kWh_xx_xxxxxx
AI
AC_Period_Minute_xx_xxxxxx
BV
AC_Power_xx_xxxxxx
BV
AC_Cool_Limit_set_xx_xxxxxx
BV
AC_Heat_Limit_set_xx_xxxxxx
BI
AC_FilterSign_xx_xxxxxx
BO
AC_FilterSign_Reset_xx_xxxxxx
MV
AC_Operation_Mode_xx_xxxxxx
MV
AC_FanSpeed_xx_xxxxxx
MV
AC_FanFlow_xx_xxxxxx
MV
AC_Mode_Limit_xx_xxxxxx
MV
AC_Remocon_Limit_xx_xxxxxx
AI
AC_Error_Code_xx_xxxxxx
BV
AC_SPI_xx_xxxxxx
BV
AC_MDS_xx_xxxxxx
NC
AC_Notify_xx_xxxxxx
AV
AC_DisCoolTemp_Set_xx_xxxxxx
AV
AC_DisHeatTemp_Set_xx_xxxxxx
AI
AC_DisCurrentTemp_xx_xxxxxx
Unit
Status value
Inactive Active
Text-1
Text-2
Text-3
Text-4 Text-5
°C
°C
°C
°C
kWh
Minute
kWh
Minute
Off
On
False
True
False
True
False
True
False
True
Auto
Cool
Heat
Fan
Auto
Low
Mid
High Turbo
None
Vertical
Horizon
All
No
Cool
Heat
Limit
Only
Only
Disable
Conditional
Enable RC
RC
RC
Refer to list of error code
False
True
False
True
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
°C/F
°C/F
°C/F
Dry

Hide quick links: