Mounting The Position Sensor With Direct Attachment - Samson 3730-2 Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

4.7.1
Mounting the position
sensor with direct at-
tachment
Type 3277-5 Actuator with 120 cm²
(Fig. 15)
The signal pressure from the positioner is
routed over the signal pressure connection of
the connecting plate (9, Fig. 15 left) to the
actuator diaphragm chamber. To proceed,
first screw the connecting plate (9) included
in the accessories onto the actuator yoke.
20
21
Symbol
Marking
Fig. 15: Mounting for Type 3277-5 Actuator (left) and Type 3277 Actuator (right)
EB 8384-2 EN
Attachment to the control valve – Mounting parts and accessories
1
2
3
11
1.1
1.2
9
Signal pressure
extends
− Turn the connecting plate (9) so that the
correct symbol for the fail-safe action
"actuator stem extends" or "actuator stem
retracts" is aligned with the marking
(Fig. 15, below).
− Make absolutely sure that the gasket for
the connecting plate (9) is correctly insert-
ed.
− The connecting plate has threaded holes
with NPT and G threads. Seal the thread-
ed connection that is not used with the
rubber seal and square plug.
Signal pressure
Vent plug
Actuator stem
retracts
1
Lever
1.1
Nut
1.2
Disk spring
2
Follower pin
3
Follower clamp
9
Connecting plate
11
Cover
20
Position sensor
21
Mounting plate
43