Error codes –
Recommended action
58 Zero point
Status classification [Maintenance required]
Recommended
action
59 Auto-correction
Status classification [No message]
Recommended
action
60 Fatal error
Additional indication at
the fault alarm contact
Status classification Maintenance alarm (cannot be classified)
Recommended
action
EB 8384-2 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Zero point incorrect
Error can occur when the positioner's attachment position is shifted or when
the valve trim is worn, particularly with soft-sealed plugs.
Check valve and attachment of the positioner. If OK, perform a zero calibra-
tion over Code 6 (see section 7.7).
We recommend to re-initialize the positioner if zero deviates by more than
5 %.
Errors in the positioner's data section are detected detected by automatic
monitoring and corrected automatically.
Automatic
Error in safety-relevant data that cannot be corrected automatically. Possible
cause: EMC disturbances.
The valve is moved to fail-safe position.
Reset over Code 36 – Std. Re-initialize the positioner.
Code list