Code list
Error codes – Recommended
action
69
Potentiometer
parameter
Additional indication at the
fault alarm contact
Status classification
Recommended action Confirm error, perform a reset and re-initialize the positioner.
70
Calibration
Additional indication at the
fault alarm contact
Status classification
Recommended action Return positioner to SAMSON AG for repair.
71
General parameters
Status classification
Recommended action Confirm error. Check and, if necessary, change the settings of the re-
73
Internal device
error 1
Status classification
Recommended action Return positioner to SAMSON AG for repair.
75
Info parameters
Status classification
Recommended action Confirm error.
100
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Error in digital potentiometer parameter
[Maintenance required]
Error in data from production calibration. The positioner continues
operation with cold start values.
[Maintenance required]
Error in parameters not critical to control operation.
[Maintenance required]
quire parameters.
Internal device error
[Maintenance required]
Error in information parameters not critical to closed-loop control opera-
tion.
[Maintenance required]
Check and, if necessary, change the settings of the require parameters.
EB 8384-2 EN