Samson 3730-2 Mounting And Operating Instructions page 14

Electropneumatic positioner
Table of Contents

Advertisement

Design and principle of operation
Type 3730-2 Positioner
Temperature
Influences
Supply air
Effect of vibration
Electromagnetic compatibility
Electrical connections
Degree of protection
Use in safety-instrumented
systems (SIL)
Emergency venting at 0 mA set
point and using optional
solenoid valve
Explosion protection
Communication (local)
Software requirements (SSP)
Binary contacts
For connection to
Two software limit switches, reverse polarity protection, floating, configurable switching characteristics (default settings
in table)
Version
Signal state
No response
Response
One fault alarm contact, floating
Version
Signal state
No fault alarm
Fault alarm
14
The technical data for the explosion-protected devices may be restricted by the
limits specified in the test certificates.
≤0.15 %/10 K
None
≤ 0.25 % up to 2000 Hz and 4 g according to IEC 770
Complying with EN 61000-6-2, EN 61000-6-3, EN 61326-1 and NAMUR Rec-
ommendation NE 21
One M20 x 1.5 cable gland for 6 to 12 mm clamping range
Second M20 x 1.5 threaded connection additionally available
Screw terminals for 0.2 to 2.5 mm² wire cross-section
IP 66/NEMA 4X
Observing the requirements of IEC 61508, the systematic capability of the pilot
valve for emergency venting as a component in safety-instrumented systems is
given.
Use is possible on observing the requirements of IEC 61511 and the required
hardware fault tolerance in safety-instrumented systems up to SIL 2 (single device/
HFT = 0) and SIL 3 (redundant configuration/HFT = 1).
See Table Summary of explosion protection certificates for Type 3730-2 Positioner
SAMSON SSP interface and serial interface adapter
TROVIS-VIEW with database module 3730-2
For connection to the binary input of the PLC
acc. to IEC 61131-2, P
max
connection to NAMUR switching amplifier acc.
to EN 60947-5-6
No explosion protection
Non-conducting
Conductive (R = 348 Ω)
No explosion protection
Conductive (R = 348 Ω)
Non-conducting
= 400 mW or for
NAMUR switching amplifier
acc. to EN 60947-5-6
Ex
≤1.0 mA
≥2.2 mA
Ex
≥2.2 mA
≤1.0 mA
EB 8384-2 EN