Change pressure limit and control parame-
ters:
Note
Do not change the pressure limit (Code 16).
Only change the control parameters K
(Code 17) and T
(Code 18) if the settings of
V
the the replaced positioner are known.
Turn
 Code 16/17/18
Press
, Code 16/17/18 blinks.
Turn
to set the control parameter selected.
Press
to confirm the setting.
EB 8384-2 EN
P
Pressure limit
Default: No
K
level
P
Default 7
T
level
V
Default 2
Enter closing direction and blocking position:
mm
Turn
 Code 34
Press
, Code 34 blinks.
Turn
 Closing direction (CCL = counter-
clockwise/CL = clockwise)
Press
.
Turn
 Code 35
Press
, Code 35 blinks.
Turn
 Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Set the fail-safe position:
Î Set switch for fail-safe position AIR TO
OPEN or AIR TO CLOSE according to
section 7.1.
Î Set volume restriction as described in
section 7.2.
Start initialization:
Î Press INIT key.
The positioner switches to MAN mode.
The blocking position is indicated.
Start-up and settings
Closing direction (direction of
rotation causing the valve to
move to the CLOSED position
(view onto positioner display)
Default: CCL (counterclockwise)
Blocking position
Default 0
73