Fail-Safe Position (Safe) - Samson 3730-2 Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

%
Switching to
manual mode (MAN)
Turn
 Code 0
Press
, display: AUtO, Code 0 blinks.
Turn
 MAN
Press
. The positioner changes to the man-
ual mode ( ).
The manual mode starts using the last set
point of the automatic mode, ensuring a
bumpless changeover. The current position is
displayed in %.
Adjust the manual set point
%
Turn
 Code 1
Press
, Code 1 blinks.
Turn
until sufficient pressure has been
built up in the positioner and the control
valve moves to the required position.
EB 8384-2 EN
Automatic mode
%
Note
The positioner automatically returns to
Code 0 if no settings are made within
120 seconds, but remains in the manual
mode.
Switch to
automatic mode
Turn
 Code 0
Press
, Code 0 blinks.
Turn
 AUtO
Press
. The positioner switches to automat-
ic mode.
8.2.2

Fail-safe position (SAFE)

If you want to move the valve to the fail-safe
position determined during start-up (see sec-
tion 7.1), proceed as follows:
Turn
 Code 0
Press
, display: current operating mode
(AUTO or MAN), Code 0 blinks.
Turn
 SAFE
Press
, display: S
The valve moves to the fail-safe position.
If the positioner has been initialized, the cur-
rent valve position in % is indicated on the
display.
Exit the fail-safe position
Turn
 Code 0
Operation
77