Error appendix
Error codes – Recommended
action
65
Hardware
Additional indication at
the fault alarm contact
Status classification
Recommended action Confirm error and return to automatic mode, or perform a reset and
66
Data memory
Additional indication at
the fault alarm contact
Status classification
Recommended action Return positioner to SAMSON AG for repair.
67
Check calculation
Additional indication at
the fault alarm contact
Status classification
Recommended action Confirm error. If this is not possible, return positioner to SAMSON AG
Data errors
Error codes – Recommended
action
68
Control parameters
Additional indication at the
fault alarm contact
Status classification
Recommended action Confirm error, perform a reset and re-initialize the positioner.
EB 8384-2 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Initialization key jammed (firmware version R 1.51 and higher)
A hardware error has occurred. The positioner changes to the fail-safe
position (SAFE).
[Maintenance alarm]
re-initialize the positioner. If this is not successful, return positioner to
SAMSON AG for repair.
No more data can be written to the memory, e.g. because written data
deviate from read data. The valve moves to the fail-safe position.
Maintenance alarm (cannot be classified)
Hardware controller monitored by test calculation.
[Maintenance alarm]
for repair.
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Error in control parameters.
[Maintenance required]
Code list