7.4 Limiting the signal pressure

If the maximum actuator force may cause
damage to the valve, the signal pressure
must be limited.
Enable configuration at the positioner before
limiting the signal pressure:
Note
If no settings are entered within 120 sec-
onds, the enabled configuration function be-
comes invalid.
Turn
g Code 3, display: No
Press
, Code 3 blinks.
Turn
 YES
Press
, display:
EB 8384-2 EN
Enable configuration
Default: No
Limit the signal pressure:
Turn
 Code 16
Press
, Code 16 blinks.
Turn
until the required pressure limit
(1.4/2.4/3.7 bar) appears.
Press
to confirm the pressure limit setting.
7.5 Checking the operating
range of the positioner
To check the mechanical attachment and the
proper functioning, the valve should be
moved through the operating range of the
positioner in the
manual set point.
Select
manual mode:
Turn
 Code 0
Press
, Code 0 blinks.
Turn
 MAN
Press
. The positioner changes to the man-
ual mode ( ).
Start-up and settings
Pressure limit
Default: No
manual mode with the
Operating mode
Default MAN