Standby

3. Standby

3.1

Restart Standby

This function is used to forcedly turn OFF the thermostat for a period of 2 minutes after a compressor stops running, in
order to prevent the frequent ON-OFF operations of the compressor and equalize pressure in the refrigerant circuit.
Furthermore, the outdoor fan continues residual operation for a while to facilitate pressure equalization and prevent the
stay of refrigerant in evaporator.
Actuator
Compressor 1
Compressor 2
Compressor 3
Outdoor unit fan1
Outdoor unit fan2
Electronic expansion valve
(Main)
Electronic expansion valve
(Subcooling)
Electronic expansion valve
(Refrigerant charge)
Solenoid valve (Refrigerant
regulator gas purging pipe)
Four way valve (Heat
exchanger switch)
Solenoid valve (Refrigerant
regulator liquid pipe)
Solenoid valve (Hot gas)
Solenoid valve (Main bypass) SVE
Solenoid valve (Refrigerant
regulator discharge pipe)
Solenoid valve (Refrigerant
regulator discharge pipe)
Four way valve (High/low
pressure gas pipe switch)
Ending conditions
3.2

Crankcase Heater Control

In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to control
the crankcase heater.
Crankcase heater
85
Elect.
Symbol
symbol
RTSQ8P
M1C
M2C
M3C
Ta>30°C: STEP4
MF1
Ta≤30°C: OFF
MF2
EVM
Y1E
EVT
Y3E
EVJ
Y2E
SVG
Y1S
20SA
Y3S
SVL
Y4S
SVP
Y5S
Y6S
SVO
Y7S
SVT
Y8S
20SB
Y2S
Discharge pipe
temperature < 70°C
OFF
Discharge pipe
temperature > 75°C
Operation
RTSQ10•12P
OFF
OFF
OFF
Ta>30°C: STEP4
Ta≤30°C: OFF
0 pls
0 pls
80 pls
OFF
Holds
OFF
OFF
OFF
OFF
OFF
Holds
2 min.
Crankcase heater
SiBE31-801_C
RTSQ14•16P
OFF
OFF
OFF
Ta>30°C: STEP4
Ta≤30°C: OFF
Ta>30°C: STEP4
Ta≤30°C: OFF
ON
Function