Field Setting
3.1.7 Centralized Control Group No. Setting
BRC1E Type
In order to conduct the centralized remote control using the centralized remote controller and
the unified ON/OFF controller, Group No. settings should be made by group using the operating
remote controller.
Make Group No. settings for centralized remote control using the operating remote controller.
(1) <Basic screen>
(2) <Field setting menu screen>
(3) <Group No. setting>
(3) <Group No. setting (Group)>
Note:
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
161
For wireless remote controller, see the following.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.
1. Press and hold Cancel button for 4 seconds or more.
Field setting menu in displayed.
Group No. setting
2. Select
Menu/Enter button.
Group No. setting screen is displayed.
3. Select Group No. setting (Group), and press Menu/Enter
button.
Group No. setting (Group) screen is displayed.
4. Select the group No. by using
Press Menu/Enter button.
SiBE31-801_C
in the field setting menu, and press
(Up/Down) button.
Test Operation