Restart Standby - Daikin VRV II RXYQ5MY1B Service Manual

R-410a heat pump 50hz
Hide thumbs Also See for VRV II RXYQ5MY1B:
Table of Contents

Advertisement

Special Control
3.5

Restart Standby

Actuator
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
Hot gas bypass valve (SVP)
Oil equalization valve (SVO)
Receiver gas discharging valve (SVG)
Non-operating unit liquid pipe stop
valve (SVSL)
Ending conditions
* Actuators are based on RXYQ16M.
90
Operation
OFF
Ta>30°C: STEP5
Ta≤30°C: OFF
Holds ON
0 pls
0 pls
OFF
ON
OFF
ON
5 min.
Remarks
In the case of RXYQ5M , this valve
turns ON.
In the case of slave units, this valve
turns OFF.
SiE39-404
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents