2. Stopping Operation
2.1
When System is in Stop Mode
Both master units and slave units all stop according to the following contents.
Actuator
Compressor 1
Compressor 2
Compressor 3
Outdoor unit fan1
Outdoor unit fan2
Electronic expansion valve
(Main)
Electronic expansion valve
(Subcooling)
Electronic expansion valve
(Refrigerant charge)
Solenoid valve (Refrigerant
regulator gas purging pipe)
Four way valve (Heat
exchanger switch)
Solenoid valve (Refrigerant
regulator liquid pipe)
Solenoid valve (Hot gas)
Solenoid valve (Main bypass)
Solenoid valve (Refrigerant
regulator discharge pipe)
Solenoid valve (Refrigerant
regulator discharge pipe)
Four way valve (High/low
pressure gas pipe switch)
Ending conditions
2.2
Stop due to Malfunction
In order to protect compressors, if abnormal conditions occur, the system will make "stop with thermostat OFF" and the
malfunction will be determined according to the number of retry times.
(Refer to P.213~215 "List of Malfunction Code" in Part 6 "Troubleshooting" about the items of malfunction decision.)
Operation by which this malfunction is determined: The system makes a stop and the remote controller displays the
relevant "Malfunction code".
Function
Elect.
Symbol
symbol
—
M1C
—
M2C
—
M3C
—
M1F
—
M2F
EVM
Y1E
EVT
Y3E
EVJ
Y2E
SVG
Y1S
20SA
Y3S
SVL
Y4S
SVP
Y5S
SVE
Y6S
SVO
Y7S
SVT
Y8S
20SB
Y2S
—
Operation
RTSQ8P
RTSQ10•12P
OFF
—
—
OFF
—
80 pls
Holds
Holds
Indoor unit thermostat is turned ON.
Stopping Operation
RTSQ14•16P
OFF
OFF
OFF
OFF
—
OFF
OFF
OFF
—
OFF
0 pls
0 pls
OFF
OFF
OFF
OFF
OFF
OFF
84