SiBE31-801_C
5.2

Startup Control in Heating Operation

Actuator
Compressor 1
Compressor 2
Compressor 3
Outdoor unit fan 1
Outdoor unit fan 2
Electronic expansion
valve (Main)
Electronic expansion
valve (Subcooling)
Electronic expansion
valve (Refrigerant
charge)
Solenoid valve
(Refrigerant regulator gas
purging pipe)
Four way valve
(Heat exchanger switch)
Solenoid valve
(Refrigerant regulator
liquid pipe)
Solenoid valve (Hot gas)
Solenoid valve (Main
bypass)
Solenoid valve
(Refrigerant regulator
discharge pipe)
Solenoid valve
(Refrigerant regulator
discharge pipe)
Four way valve (High/low
pressure gas pipe switch)
Ending conditions
Function
Pressure
Elect.
equalization
Symbol
symbol
control
before startup
M1C
M2C
0 Hz
M3C
M1F
STEP4
M2F
EVM
Y1E
0 pls
EVT
Y3E
0 pls
EVJ
Y2E
80 pls
SVG
Y1S
OFF
20SA
Y3S
ON
SVL
Y4S
OFF
SVP
Y5S
OFF
SVE
Y6S
OFF
SVO
Y7S
OFF
SVT
Y8S
OFF
20SB
Y2S
OFF
A lapse of 60
sec.
Startup control
STEP1
52 Hz+OFF+OFF
20SA=ON: STEP7
20SA=ON: SH Control
0 pls
80 pls
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
A lapse of 15 sec.
Startup Control
STEP2
52Hz+OFF+OFF+2STEP / 20
sec.
(Until it reaches
Pc-Pe>0.39 MPa)
20SA=ON: STEP7
20SA=ON: SH Control
0 pls
80 pls
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
• A lapse of 90 sec.
OR
• Pc - Pe>0.39 MPa
88