Daikin RTSQ20PY1 Service Manual page 182

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

Field Setting
a. "Setting mode 1"
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group
• COOL/HEAT selection (SLAVE)················Used to select COOL or HEAT by outdoor unit group
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Normally, "Setting mode 1" is set. In
case of other status, push MODE
(BS1) button one time and set to
"Setting mode 1".
Push the SET (BS2) button to set the
blinking of LED to any of conditions
shown on the right.
Push the RETURN (BS3) button to
determine the setting.
Procedure for checking check items
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pushing the RETURN (BS3) button
will bring the system to the initial state
of "Setting mode 1".
171
unit (factory setting).
with the master unit.
with the slave unit.
Setting (displaying) item
For selection by individual outdoor unit (factory setting)
For selection in a batch of outdoor unit group with master unit
For selection in a batch of outdoor unit group with slave unit
Pushing the RETURN (BS3) button will return the system to the initial condition of
"Setting mode 1".
COOL/HEAT select
MODE
TEST
IND
MASTER
H1P
H2P
H3P
H4P
h
h
k
h
COOL/HEAT select
MODE
TEST
IND
MASTER
H1P
H2P
H3P
H4P
h
h
l
h
h
h
h
h
h
Low
Demand
noise
SLAVE
H7P
H6P
H5P
h
h
h
Current operating conditions
Setting of COOL/HEAT selection
khhBy individual outdoor
hkhIn a batch of outdoor unit
hhkIn a batch of outdoor unit
Low noise operating conditions
Demand operating conditions
SiBE31-801_C
k ON
h OFF
l Blink
Low
Demand
noise
SLAVE
H7P
H6P
H5P
h
h
h
h
l
h
h
h
h
l
h
h
hNormal kAbnormal
lIn preparation or in
check operation
unit
group with master unit
group with slave unit
hIn normal operation
kIn low noise operation
hIn normal operation
kIn demand operation
Test Operation