Specifications
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Power Supply Intake
Notes
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Power Supply Intake
Notes
23
FXCQ20M8V3B
FXCQ25M8V3B
1
Hz
50
V
230
A
0.50
A
16.00
A
0.40
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
FXCQ63M8V3B
1
Hz
50
V
230
A
0.90
A
16.00
A
0.70
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
FXCQ32M8V3B
V3
1
1
50
50
230
230
0.50
0.50
16.00
16.00
0.40
0.40
-10%
+10%
Both indoor and outdoor unit
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA<= 4 × FLA
select wire size based on the MCA
instead of a fuse, use a circuit breaker
Finally, click on the document title of your choice.
FXCQ80M8V3B
V3
1
50
230
1.10
16.00
0.90
-10%
+10%
Both indoor and outdoor unit
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA<= 4 × FLA
select wire size based on the MCA
instead of a fuse, use a circuit breaker
Finally, click on the document title of your choice.
SiBE31-801_C
FXCQ40M8V3B
FXCQ50M8V3B
1
1
50
50
230
230
0.80
0.80
16.00
16.00
0.60
0.60
FXCQ125M8V3B
1
50
230
1.30
16.00
1.00
Specifications