Troubleshooting (Heat Reclaim Ventilation)
CHECK 4
Power Transistor Check
Perform the following procedures prior to check.
(1) Power Off.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
[Preparation]
· Tester
[Point of Measurement and Judgement Criteria]
· Measure the resistance value using a tester at each point of measurement below, 10 minutes later after power OFF.
To use analog tester:
Measurement in the resistance value mode in the range of
multiplying 1kΩ.
Point of Measurement
No.
+
1
P2
U
2
P2
V
3
P2
W
4
U
P2
5
V
P2
15kΩ and
6
W
P2
above
7
N3
U
(including ∞)
8
N3
V
9
N3
W
10
U
N3
11
V
N3
12
W
N3
[PCB and Circuit Diagram]
341
Judgement
Remarks
Criteria
2 ~ 15kΩ
Due to condenser
charge and so on,
resistance
measurement may
require some time.
2 ~ 15kΩ
J1
J2
J3
* Preparing a tester in the analog system is recommended.
A tester in the digital system with diode check function will
be usable.
To use digital tester:
Measurement is executed in the diode check mode. (
Point of Measurement
No.
+
1
P2
2
P2
3
P2
4
U
5
V
6
W
7
N3
8
N3
9
N3
10
U
11
V
12
W
P1
P3
P1
DM
X10A K2
J1
L1
J2
L2
L3
J3
Judgement
Remarks
Criteria
U
Due to condenser charge and
1.2V and over
so on, resistance measurement
V
may require some time.
W
P2
P2
P2
0.3 ~ 0.7V
U
V
W
N3
Due to condenser charge and
1.2V and over
so on, resistance measurement
N3
may require some time.
N3
W
V
N3 U
P2 P3
IGBT
N3
U
V
W
X11A
Troubleshooting
SiBE31-801_C
)