SiBE31-801_C
<Disable-operation setting of the compressor> (Applied model: RTSYQ10~16P)
k Disabling the inverter compressor from operating
Set No. 42 of setting mode 2 to "Disable-inverter compressor operation."
k Disabling the STD compressor 1 (or STD compressor 2) from operating
Set No. 19 of setting mode 2 to "Disable-STD compressor 1 or 2 operation."
k Disabling the STD compressor 2 from operating [RTSQ14 · 16P]
Set No. 19 of setting mode 2 to "Disable-STD compressor 2 operation."
• On the models RTSQ14P and 16P, if the INV compressor is set to "Operation prohibited",
• On the models RTSQ14P and 16P, the STD compressor 1 cannot be set to "Operation
Test Operation
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 42 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Step)
(1) Press the MODE button (BS1) for 5
seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
only one STD compressor will operate due to oil equalization.
prohibited" due to oil equalization.
k
h
l
LED display (
: ON
: OFF
H1P-----------H7P
k h h h h h h
k k h k h k h
k h h h h h l
k h h h h l h
k h h h h h h
h h k h h h h
k
h
l
LED display (
: ON
: OFF
H1P-----------H7P
k h h h h h h
k h k h h k k
k h h h h h h
k h h h h h l
k h h h h h h
h h k h h h h
k
h
l
LED display (
: ON
: OFF
H1P-----------H7P
k h h h h h h
k h k h h k k
k h h h h h h
k h h h h l h
k h h h h h h
h h k h h h h
Field Setting
: Blink)
: Blink)
: Blink)
190