Daikin RTSQ20PY1 Service Manual page 55

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
Wall Mounted Unit
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
Specifications
FXAQ20PV1
FXAQ25PV1
Hz
V
A
0.3
0.4
A
A
0.2
0.3
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
FXAQ32PV1
FXAQ40PV1
VE
1~
50
220-240
0.4
0.4
15
0.3
0.3
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
Specifications
FXAQ50PV1
FXAQ63PV1
0.4
0.6
0.3
0.5
44

Hide quick links: