Troubleshooting by Remote Controller
6. Error Display
7. Unit No. Transfer
8. Sensor Address
209
Service Menu
1. Warning display ON
Selection
2. Warning display OFF No warning is displayed.
3. Error display ON
4. Error display OFF
1. Current Unit No.
2. Transfer Unit No.
Unit No.: 0 - 15
Display
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
Data
Item 2
Displays a warning on the screen if an error
occurs.
Displays the error on the screen.
Displays neither errors nor warnings.
A unit No. can be transferred to another.
Select the Unit No. you want to check.
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/heating batch address No.
Demand/low-noise address No.
The corresponding data will be displayed, based
on the Unit No. and Code selected.
SiBE31-801_C
Remarks
Troubleshooting