Ja" Outdoor Unit: Malfunction Of High Pressure Sensor - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
JA
4.33 "
" Outdoor Unit: Malfunction of High Pressure Sensor
JA
Remote
Controller
Display
Applicable
RTSQ8P~16P (Outdoor Unit), BTSQ20P (Function Unit)
Models
Method of
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Detection
Malfunction
When the high pressure sensor is short circuit or open circuit.
(Not less than 4.22MPa, or 0.01MPa and below)
Decision
Conditions
Supposed
Causes
Troubleshooting
Defect of high pressure sensor system
Connection of low pressure sensor with wrong connection.
Defect of outdoor unit PCB (A1P).
Defective connection of high pressure sensor
Troubleshooting by Indication on the Remote Controller
270