Daikin RTSQ20PY1 Service Manual page 59

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
Concealed Floor Standing Unit
1-2 ELECTRICAL SPECIFICATIONS
Power
Name
Supply
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps
(MFA)
Full load amps (FLA)
Voltage
Minimum
range
Maximum
Notes
Specifications
FXNQ20MAVE
FXNQ25MAVE
Hz
V
A
0.3
0.3
A
15
15
A
0.2
0.2
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
Maximum allowable voltage range variation between phases is 2%.
FXNQ32MAVE
FXNQ40MAVE
VE
1~
50
220-240
0.6
0.6
15
15
0.5
0.5
-10%
+10%
above listed range limits.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
Specifications
FXNQ50MAVE
FXNQ63MAVE
0.6
0.6
15
15
0.5
0.5
48

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rtsq16py1Rtsq14py1Rtsq10py1

Table of Contents