Access Control; B901; Address Settings; Supervision - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

86
en | Access control
15

Access control

The control panel supports access control using the B901 Access Control Module and the
D9210C Access Control Interface Module.
Any of the following can grant access:
The control panel access control features can deny access when the system in On (armed).
The control panel can also grant access only to certain authorized users depending on
whether the area is all on, part on, or off. Programming for automatic disarming when
designated authorized users are granted access is also possible.
The Dual Authentication feature can optionally require passcode entry with presentation of
door credentials before access authorization is granted.
15.1

B901

The B901 Access Control Interface Module is a fully supervised, addressable SDI/SDI2 bus
device that allows access control integration for Bosch compatible control panels. This
module offers 14 programmable levels of access authority. Authority for access is controlled
by the user level, the group of the user, the time of day, the door state, and the area armed
state. Control each authority restriction through automatic and manual functions.
The module connects to the control panel with the SDI2 bus or the SDIx bus configured as SDI
using terminals 27 through 30 (or 23 through 26 if configured for SDI2), or using the
interconnect wiring connector. You can connect more than one module to the control panel by
wiring them in parallel. This section includes basic installation instructions. For detailed
installation instructions, refer to the Access Control Module (B901) Installation and Operation
Guide.
15.1.1

Address settings

Notice!
The module reads the address switch setting only during module power up. If you change the
setting after you apply power to the module, you must cycle the power to the module in order
for the new setting to take effect.
If multiple access control modules reside on the same system, each access control module
must have a unique address.
For valid addresses, refer to B901 address settings, page 171.
15.1.2

Supervision

With any failure to receive an expected response from the module, all keypads show a system
fault. The control panel sends a module trouble report to the central station (if configured for
module trouble reports).
15.1.3

Installation and control panel wiring (B901)

Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 66.
2016.06 | 08 | F.01U.303.996
Wiegand-style access control device (card reader) connected to the access control
module
Request to enter (RTE) or request to exit (REX) input
Unlock command on an SDI2 keypad (excluding fire keypads)