88
en | Program and test the control panel
16

Program and test the control panel

When you complete the hardware installation, reconnect the battery, and then plug in the
transformer. Next, program the control panel, and then test the control panel and
configuration.
Notice!
After system installation and any control panel programming, perform a complete system test
(a UL 864 requirement). A complete system test includes testing the control panel, all
devices, and communication destinations for proper operation.
16.1

Program the control panel

Use RPS or a keypad to program the control panel. Refer to RPS Help and Keypad Installer
menu, page 115.
16.2

Perform walk tests

When you perform a walk test, the control panel includes only points assigned to areas within
the keypad's scope, based on the walk test type chosen. During a walk test, the points do not
process normally, and only indicate that they were tested. You can perform four different
types of walk tests on this system.
Each walk test type automatically terminates after 20 min of inactivity.
All point verification is disabled for all points during any walk test.
The control panel sends Walk Test Start and Walk Test End reports to the central station.
16.2.1

Fire walk test

A fire walk test allows you to test all visible, 24-hr points.
A fire walk test includes multiple point types. Points must meet the following criteria:
Performing a fire walk test:
1.
2.
3.
4.
5.
Notice!
If the point loop has multiple detectors, then the keypad will emit a tone as confirmation for
each fault detected.
16.2.2

Intrusion walk test

An intrusion walk test includes points meeting the following criteria:
2016.06 | 08 | F.01U.303.996
Have a point source other than Unassigned
Have a point index not set to Disabled (must be non-zero)
Are not service bypassed
Are not invisible points
Have a point type of Keyswitch maintained, Keyswitch momentary, Open/Close Point,
Fire, Aux AC Supervision, or Gas
Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
Open the Main menu and then go to the [3] Actions menu > [3] Test > [1] Walk Test > [1]
Fire option.
The keypad shows the number of points that remain untested.
To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use
/[PREV] or
When you fault a point (press the test button on a smoke detector for example), the
keypad emits a brief tone and shows the point name.
Installation and System Reference Guide
/[NEXT].
Control Panels
Bosch Security Systems, Inc.