Off-Board Points; B208 Octo-Input Module; Sdi2 Address Settings; Supervision - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panels
13

Off-board points

The control panel supports off-board points using the B208 Octo-input Module, the B299
POPEX Module, and the B600 Retrofit ZONEX Module.
13.1

B208 Octo-input Module

The B208 Octo-input Module is an eight point expansion device that connects to the control
panel through the SDI2 bus. This module is supervised and communicates back to the control
panel all point status changes. The module points work in the same way as the points on the
control panel.
B9512G control panels support up to 59 modules. B8512G support up to 9 modules.
The module connects to the SDI2 bus on the control panel using terminals 27 through 30 (or
23 through 26 if configured for SDI2), or using the SDI2 interconnect wiring connector. You
can connect more than one module to the control panel by wiring them in parallel. This
section includes basic installation instructions. For detailed installation instructions, refer to
the Octo-input Module (B208) Installation and Operation Guide.
Notice!
Do not connect fire and non-fire devices to the same B208 Octo-input Module in a UL
commercial fire installation.
13.1.1

SDI2 address settings

Notice!
The module reads the address switch setting only during module power up. If you change the
setting after you apply power to the module, you must cycle the power to the module in order
for the new setting to take effect.
If multiple B208 modules reside on the same system, each B208 module must have a unique
address.
The control panel model determines the number of points allowed and the valid addresses.
For valid point and address numbers, refer to B208 address settings, page 168.
13.1.2

Supervision

The control panel automatically enables supervision of B208 Octo-input Modules on the SDI2
bus when an associated point has its source programmed for Octo-input.
With any failure to receive an expected response from the module, all keypads show a system
fault. The control panel sends a module trouble report to the central station (if configured for
module trouble reports).
13.1.3

Installation and control panel wiring (B208)

Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 66.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Install the module
1.
Bosch Security Systems, Inc.
Set the module address using the address switches before you install it in the enclosure.
Installation and System Reference Guide
Off-board points | en
75
2016.06 | 08 | F.01U.303.996

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512g-eB8512g-eB8512g

Table of Contents

Save PDF