B426 Ethernet Communication Module; Address And Emulation Settings; Supervision; B426 Module Faults - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

52
en | IP communications
Flash pattern
3 quick flashes
Tab. 8.5: Cellular module diagnostic LED patterns
8.3

B426 Ethernet Communication Module

The B426 Conettix Ethernet Communication Module is a four-wire powered SDI2 device that
provides connection for two-way communication over Ethernet networks to the control panels.
The control panel supports two modules.
The B426 Conettix Ethernet Communication Module connects to the SDI2 bus on the control
panel using terminals 27 through 30 (or 23 through 26 if configured for SDI2), or using the
SDI2 interconnect wiring connector. This section includes basic installation instructions. For
detailed installation instructions, refer to the Conettix Ethernet Communication Module (B426)
Installation and Operation Guide (P/N: F01U281208).
8.3.1

Address and emulation settings

Notice!
The module reads the address switch setting only during module power up. If you change the
setting after you apply power to the module, you must cycle the power to the module in order
for the new setting to take effect.
Set the address switch to 1 or 2.
If multiple B426 modules reside on the same system, each B426 module must have a unique
address.
8.3.2

Supervision

The control panel supervises in two ways:
8.3.3

B426 module faults

With a B426 installed, several services become available to the control panel. Any break in the
Ethernet connection to a supervised B426 results in a system fault at the keypads indicating
Open Cable trouble.
If a Domain Name Server (DNS) is available on the network, a failure to resolve an individual
Network Address hostname results in a system fault at the keypads indicating DNS ERROR ##.
The error number represents the communication module and destination combination that
failed. Refer to RPS Help or the control panel's Program Entry Guide for details on
communication module/destination combinations. The keypad shows a failure to resolve the
domain name used for RPS Network Address.
2016.06 | 08 | F.01U.303.996
Off
Module supervision. The control panel supervises the module through polling. If the
module does not respond to the control panel polling, the control panel declares the
device missing.
Communication supervision. The control panel supervises the communication path by
polling the central station receiver. If the poll is missed from either side, a communication
fault is declared both at the control panel and the central station receiver.
Installation and System Reference Guide
Function
Communication error state. Indicates the
module is unable to communicate on the
cellular network.
LED trouble state. Module is not powered, or
some other trouble condition prohibits the
module from controlling the heartbeat LED.