90
en | Program and test the control panel
–
–
–
–
Performing an invisible walk test:
1.
2.
3.
4.
2016.06 | 08 | F.01U.303.996
Have a point source other than Unassigned
Have a point index not set to Disabled (must be non-zero)
Have a point index configured with the point type of 24-Hour, Part On, Interior, or Interior
Follower
Are not service bypassed
Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
Enter your passcode and press [ENTER]. The keypad shows the number of points that
remain to be tested.
To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use
/[PREV] or
When your fault a point (open a door for example), the keypad emits a brief tone and
shows the name.
Installation and System Reference Guide
/[NEXT].
Control Panels
Bosch Security Systems, Inc.